ARI34036020040503

上传人:沈*** 文档编号:78941486 上传时间:2022-04-22 格式:DOC 页数:22 大小:553.50KB
收藏 版权申诉 举报 下载
ARI34036020040503_第1页
第1页 / 共22页
ARI34036020040503_第2页
第2页 / 共22页
ARI34036020040503_第3页
第3页 / 共22页
资源描述:

《ARI34036020040503》由会员分享,可在线阅读,更多相关《ARI34036020040503(22页珍藏版)》请在装配图网上搜索。

1、2004STANDARD forPERFORMANCE RATING OFCOMMERCIALANDINDUSTRIALUNITARY AIR-CONDITIONINGStandard 340/360AND HEAT PUMP EQUIPMENTIMPORTANTSAFETY DISCLAIMERARI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installe

2、d or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline.A

3、RI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. ARI does not certify or guarantee that any test conducted under its standards/guidelines will be non-hazardous or free from risk.ARI CERTIFICATION PROGRAM PROVISIONSScope of the Certi

4、fication ProgramThe Certification Program includes all air-cooled, water-cooled and evaporatively-cooled unitary air-conditioning, air-source unitary heat pump equipment, and air-conditioning condensing units rated at or above 65,000 Btu/h 19,000 W at ARI Standard Rating Conditions (Cooling) but bel

5、ow 250,000 Btu/h 73,200 W at ARI Standard Rating Conditions (Cooling).Certified RatingsThe following Certification Program ratings are verified by test:Unitary Air-Conditioners and Air-Conditioning Condensing UnitsAir-cooled, water-cooled and evaporatively-cooled from 65,000 Btu/h 19,000 W to below

6、250,000 Btu/h 73,200 W.1. ARI Standard Rating Cooling Capacity, Btu/h2. Energy Efficiency Ratio, EER, Btu/Wh3. Integrated Part-Load Value, IPLVAir-Source Unitary Heat Pump Equipment Air-cooled from 65,000 Btu/h 19,000 W to below 250,000 Btu/h 73,200 W.1. ARI Standard Rating Cooling Capacity, Btu/h2.

7、 Energy Efficiency Ratio, EER, Btu/Wh3. High Temperature Heating Standard Rating Capacity, Btu/h4. High Temperature Coefficient of Performance (COP 47EF)5. Low Temperature Heating Standard Rating Capacity, Btu/h6. Low Temperature Coefficient of Performance (COP 17EF) 7. Integrated Part-Load Value, I

8、PLVConformance to the requirements of the Maximum Operating Condition Test, Cooling Low Temperature Operation Test, Insulation Efficiency Test (Cooling), and Condensate Disposal Test (Cooling) are also verified by test.Note:This standard supersedes ARI Standard 340/360-2000.TABLE OF CONTENTSSECTIONP

9、AGESection 1.Purpose1Section 2.Scope1Section 3.Definitions1Section 4.Classifications2Section 5.Test Requirements2Section 6.Rating Requirements2 Section 7.Minimum Data Requirements for Published Ratings10Section 8.Operating Requirements10Section 9.Marking and Nameplate Data12Section 10.Conformance Co

10、nditions12TABLESTable 1.Classification of Commercial and Industrial Unitary Air-ConditioningEquipment4Table 2.Classification of Commercial and Industrial Unitary Heat Pump Equipment5Table 3.Conditions for Standard Rating and Operating Tests6Table 4.Minimum External Pressure7FIGURESFigure 1.Part-Load

11、 Factor Curve9APPENDICESAppendix A.References - Normative13Appendix B.References - Informative13Appendix C.Capacity Calculation For Unitary Equipment Using an Outdoor Air Cooling Coil Normative 14Appendix D.Method and Example of Calculating Integrated Part-LoadValues (IPLV) - Normative16TABLES FOR A

12、PPENDICESTable D1.Example IPLV Calculation (I-P Units)18FIGURES FOR APPENDICESFigure C1.Test Set-Up for Units Using an Outdoor Coil15Figure D1.Part-Load Factor Example17PERFORMANCE RATING OF COMMERCIAL AND INDUSTRIAL UNITARY AIR-CONDITIONING AND HEAT PUMP EQUIPMENTSection 1. Purpose1.1Purpose. The p

13、urpose of this standard is to establish for Commercial and Industrial Unitary Air-Conditioning and Heat Pump Equipment: definitions; classifications; test requirements; rating requirements; minimum data requirements for Published Ratings; operating requirements; marking and nameplate data; and confo

14、rmance conditions. 1.1.1Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users.1.1.2Review and Amendment. This standard is subject to review and amendment as technology advances.Section 2. Scope2.1Scope. This standard

15、 applies to factory-made Commercial and Industrial Unitary Air-Conditioning and Heat Pump Equipment as defined in Section 3.2.1.1Energy Source. This standard applies only to electrically operated, vapor compression refrigeration systems.2.2Exclusions. This standard does not apply to the following:2.

16、2.1Rating and testing of individual assemblies, such as condensing units or coils, for separate use.2.2.2Unitary Air-Conditioners as defined in ARI Standard 210/240, Unitary Air-Conditioning and Air-Source Heat Pump Equipment, with capacities less than 65,000 Btu/h 19 000 W, or to Unitary Heat Opera

17、ted Air-Conditioning Equipment, or Water-Source Heat Pumps as defined in ISO 13256-1, Water-Source Heat Pumps Testing and Rating for Performance Part I: Water-to-Air and Brine-to-Air Heat Pumps.2.2.3Rating of units equipped with desuperheater/water heating devices (as defined in ANSI/ASHRAE Standard

18、 137) in operation.Section 3. DefinitionsAll terms in this document shall follow the standard industry definitions in the current edition of ASHRAE Terminology of Heating, Ventilation Air-Conditioning and Refrigeration, unless otherwise defined in this section.3.1Coefficient of Performance. A ratio

19、of the cooling/heating capacity in watts W to the power input values in watts W at any given set of rating conditions expressed in watts/watts W/W. For heating COP, supplementary resistance heat shall be excluded.3.1.1Standard Coefficient of Performance. A ratio of the capacity to power input value

20、obtained at Standard Rating Conditions.3.2Commercial and Industrial Unitary Air-Conditioner. One or more factory-made assemblies, which includes a cooling coil, an air moving device, a compressor(s) and condenser combination, and may include a heating function as well. Where such equipment is provid

21、ed in more than one assembly, the separate assemblies shall be designed to be used together, and the requirements of rating outlined in this standard shall be based upon the use of matched assemblies.3.2.1Functions. The functions of Commercial and Industrial Unitary Air-Conditioners, either alone or

22、 in combination with a heating plant, are to provide air-circulation, cooling, dehumidification, and may include the functions of heating, humidifying, outdoor air ventilation, and air cleaning.3.3Commercial and Industrial Unitary Heat Pump. One or more factory-made assemblies, which normally includ

23、e an indoor conditioning coil, an air moving device, compressor(s), and an outdoor coil(s), including means to provide a heating function and may or may not include a cooling function. When such equipment is provided in more than one assembly, the separate assemblies shall be designed to be used tog

24、ether, and the requirements of rating outlined in the standard shall be based upon the use of matched assemblies.3.3.1Functions. Commercial and Industrial Unitary Heat Pumps shall provide the function of heating, air circulation and may include the function of air cooling, dehumidifying or humidifyi

25、ng, outdoor air ventilation, and air cleaning.3.4Cooling Capacity. The capacity associated with the change in air enthalpy which includes both the Latent and Sensible Capacities expressed Btu/h W.3.4.1Latent Capacity. Capacity associated witha change in humidity ratio.3.4.2Sensible Capacity. Capacit

26、y associated with a change in dry-bulb temperature.3.5Energy Efficiency Ratio (EER). A ratio of the Cooling Capacity in Btu/h to the power input values in watts at any given set of rating conditions expressed in Btu/Wh.3.6Integrated Part-Load Value (IPLV). A single number cooling part-load efficienc

27、y figure of merit calculated per the method described in 6.2.2.3.7Published Rating. A statement of the assigned values of those performance characteristics, under stated Rating Conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal size and

28、type (identification) produced by the same manufacturer. The term Published Rating includes the rating of all performance characteristics shown on the air-conditioner or heat pump or published in specifications, advertising, or other literature controlled by the manufacturer, at stated Rating Condit

29、ions.3.7.1Application Rating. A rating based on tests performed at application Rating Conditions (other than Standard Rating Conditions).3.7.2Standard Rating. A rating based on tests performed at Standard Rating Conditions.3.8Rating Conditions. Any set of operating conditions under which a single le

30、vel of performance results and which causes only that level of performance to occur.3.8.1Standard Rating Conditions. Rating conditions used as the basis of comparison for performance characteristics.3.9Shall or Should. Shall or should shall be interpreted as follows:3.9.1Shall. Where shall or shall

31、not is used for a provision specified, that provision is mandatory if compliance with the standard is claimed.3.9.2Should. “Should” is used to indicate provisions which are not mandatory but which are desirable as good practice.3.10Standard Air. Air weighing 0.075 lb/ft3 1.2 kg/m3 which approximates

32、 dry air at 70F 21C and at a barometric pressure of 29.92 in Hg 101.1 kPa.Section 4. ClassificationsCommercial and Industrial Unitary Air-Conditioning and Heat Pumps Equipment within the scope of this standard shall be classified as shown in Tables 1 and 2.Section 5. Test Requirements5.1All standard

33、 ratings shall be verified by tests conducted in accordance with ASHRAE Standard 37 and with the test methods and procedures as described in this standard and its appendices.Section 6. Rating Requirements6.1Standard Ratings. Standard Ratings shall be established at the Standard Rating Conditions spe

34、cified in Table 3. Standard Ratings related to cooling or heating capacities shall be net values, including the effects of circulating fan heat, but not including supplementary heat. Standard Ratings (Cooling) shall be stated as total Cooling Capacity. Standard Ratings shall be based on the total po

35、wer input to the compressor(s) and fan(s), plus controls and other items required as part of the system for standard rating operation.Standard Ratings of units which do not have indoor air-circulating fans furnished as part of the model, i.e., split systems with indoor coil alone, shall be establish

36、ed by subtracting 1250 Btu/h per 1000 cfm 775 W/m3/s from the total cooling capacity, and by adding the same amount to the heating capacity. Total power input for both heating and cooling shall be increased by 365 W per 1000 cfm 226 W/m3/s of indoor air circulated.Standard Ratings of water-cooled un

37、its from 65,000 to below 135,000 Btu/h 19,000 to 39,600 W shall include a total allowance for cooling tower fan motor and circulating water pump motor power inputs to be added in the amount of 10.0 W per 1000 Btu/h 34.1 W per 1000 W cooling capacity.6.1.1Values of Standard Capacity Ratings. These ra

38、tings shall be expressed in terms of Btu/hW as shown.Capacity Ratings, Btu/h WMultiples, Btu/h W65,000 up to 135,00019,000 up to 39,6001000 300136,000 up to 400,00039,800 up to 117,0002000 600above 400,000above 117,0005000 1,5006.1.2Values of Energy Efficiency Ratios and Coefficients of Performance.

39、 Energy Efficiency Ratios (EER) and Integrated Part-Load Values (IPLV) for cooling, whenever published, shall be expressed in multiples of the nearest 0.1. Coefficients of Performance (COP) for heating or cooling, whenever published, shall be expressed in multiples of the nearest 0.1.6.1.3 Standard

40、Rating Tests. Table 3 indicates the tests and test conditions which are required to determine values of standard capacity ratings and values of energy efficiency. Standard cooling ratings are not applicable for heating-only heat pumps.6.1.3.1Voltage and Frequency. Standard Rating tests shall be perf

41、ormed at the nameplate rated voltage(s) and frequency.For air-conditioners and heat pumps with dual nameplate voltage ratings, Standard Rating tests shall be performed at both voltages, or at the lower of the two voltages, if only a single Standard Rating is to be published.6.1.3.2Indoor-Coil Airflo

42、w Rate. All Standard Ratings shall be determined at an indoor-coil airflow rate as outlined below. All airflow rates shall be expressed in terms of Standard Air.a. Equipment with indoor fans intended for use with field installed duct systems shall be rated at the indoor-coil airflow rate (not to exc

43、eed 37.5 SCFM per 1000 Btu/h 0.06 m3/s per 1000 W of rated capacity) delivered when operating against the minimum external resistance specified in Table 4 or at a lower indoor-coil airflow rate if so specified by the manufacturer.b.Equipment with indoor fans not intended for use with field installed

44、 duct systems (free discharge) shall be rated at the indoor-side air quantity delivered when operating at 0 in H2O 0 Pa external pressure as specified by the manufacturer.c.100% recirculated air shall be used except when the rating with outside air is claimed (6.1.3.6). For units equipped for multi-

45、zone or dual duct operation, the hot deck shall be closed off using dampers supplied with the unit.d.Equipment which does not incorporate an indoor fan, but is rated in combination with a device employing a fan shall be rated as described under 6.1.3.2a. For equipment of this class which is rated fo

46、r general use to be applied to a variety of heating units, the indoor-coil airflow rate shall be the lesser of: (1) the manufacturer specified Standard Ratings, not to exceed 37.5 SCFM/1000 Btu/h 0.06 m3/s per 1000 W of rated capacity or (2) the airflow rate obtained through the indoor coil assembly

47、 when the pressure drop across the indoor coil assembly and the recommended enclosures and attachment means is not greater than 0.30 in H2O 75 Pa.e.Indoor-coil airflow rates and pressures as referred to herein apply to the airflow rate experienced when the unit is cooling and dehumidifying under the

48、 conditions specified in this section. This airflow rate, except as noted in 6.1.3.2b and 8.3, shall be employed in all other tests prescribed herein without regard to resulting external static pressure. Heating-only units shall use the airflow rate experienced when the unit is operating under the h

49、igh temperature steady-state heating standard test at Standard Rating Conditions.Table 1. Classification of Commercial andIndustrial Unitary Air-Conditioning EquipmentTypes of Commercial and Industrial Unitary Air-ConditionersDesignationARI Type1, 2ArrangementSingle PackageSP-ASP-ESP-WFANCOMP EVAPCO

50、NDYear-RoundSinglePackageSPY-ASPY-ESPY-WFANHEATCOMPEVAPCONDCondensingUnit, Coil and BlowerRCU-A-CBRCU-E-CBRCU-W-CBFANEVAPCOMPCONDYear-RoundCondensing Unit, Coil and BlowerRCUY-A-CBRCUY-E-CBRCUY-W-CBFANHEAT EVAP CONDCOMPRemoteCondenserRC-ARC-ERC-WFANEVAP COMPCONDCondensingUnit, CoilAloneRCU-A-CRCU-E-

51、CRCU-W-CEVAPCONDCOMPYear-RoundRemote CondenserRCY-ARCY-ERCY-WFANEVAPHEATCOMPCONDNote:1 A suffix of “-O” following any of the above classifications indicates equipment not intended for use with field-installed duct systems (6.1.3.2b).2 A suffix of “-A” indicates air-cooled condenser, “-E” indicates e

52、vaporatively-cooled condenser, and “-W” indicates water-cooled condenser.Table 2. Classification of Commercial and Industrial Unitary Heat Pump Equipment Types of Commercial and Industrial Unitary Heat PumpsDesignationARI Type1ArrangementHeating andCoolingHeatingOnlySingle PackageHSP-AHOSP-AFANCOMPI

53、NDOORCOILOUTDOORCOILRemote OutdoorCoilHRC-A-CBHORC-A-CBFANINDOOR COILCOMPOUTDOOR COILRemote OutdoorCoil with NoIndoor FanHRC-A-CHORC-A-CINDOOR COILCOMPOUTDOOR COILSplit SystemHRCU-A-CBHORCU-A-CBFANINDOOR COILCOMPOUTDOOR COILSplit System with No IndoorFanHRCU-A-CHORCU-A-CINDOOR COILCOMPOUTDOOR COILNo

54、te:1 A suffix of “-O” following any of the above classifications indicates equipment not intended for use with field-installed duct systems (6.1.3.2b).Table 3. Conditions for Standard Rating and Operating Tests TESTINDOOR SECTIONOUTDOOR SECTIONAir EnteringAir EnteringWaterDry-BulbF oCWet-BulbF oCAir

55、 CooledEvaporativeINF oCOUTF oCDry-BulbF oCWet-BulbF oCDry-BulbFoC Wet-BulbFoC HEATING COOLINGStandard Rating Conditions Cooling380.0 26.767.0 19.495.035.075.0123.995.035.075.023.985.029.495.035.0Low Temperature Operating Cooling367.019.457.013.967.019.457.0113.967.019.457.013.9-70.0221.1Maximum Ope

56、rating Conditions380.026.767.019.411546.175.0123.910037.880.0426.790.0232.2-Part-Load Conditions (IPLV)380.026.767.019.480.026.767.0119.480.026.767.019.475.0223.9-Insulation Efficiency380.026.775.023.980.026.775.0123.980.026.775.023.9-80.026.7Condensate Disposal380.026.775.023.980.026.775.0123.980.0

57、26.775.023.9-80.026.7 Standard Rating Conditions(High Temperature Steady State Heating)70.021.160.0 15.6 (max)478.3436.1-Standard Rating Conditions(Low Temperature Steady State Heating)70.021.160.015.6(max)17-8.315-9.4-Maximum Operating Conditions80.026.7-75.023.965.018.3-NOTES:1The wet-bulb tempera

58、ture condition is not required when testing air cooled condensers which do not evaporate condensate except for units with optional outdoor cooling coil.2Water flow rate as determined from Standard Rating Conditions Test.3Cooling rating and operating tests are not required for heating only heat pumps

59、.4Make-up water temperature shall be 90F 32C.Table 4. Minimum External Pressure1Standard Capacity RatingsMinimumExternalResistanceBtu/h x 1000W x 1000in H2OkPa65 thru 7071 thru 105106 thru 134135 thru 210212 thru 280282 thru 350352 thru 400405 thru 500505 and over19 thru 2121 thru 30.831.1 thru 39.339.6 thru 61.662.1 thru 82.182.6 thru 103103.1 thru 117118.6 thru 146147.9 and over0.200.250.300.350.400.45

展开阅读全文
温馨提示:
1: 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
2: 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
3.本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
5. 装配图网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
关于我们 - 网站声明 - 网站地图 - 资源地图 - 友情链接 - 网站客服 - 联系我们

copyright@ 2023-2025  zhuangpeitu.com 装配图网版权所有   联系电话:18123376007

备案号:ICP2024067431-1 川公网安备51140202000466号


本站为文档C2C交易模式,即用户上传的文档直接被用户下载,本站只是中间服务平台,本站所有文档下载所得的收益归上传人(含作者)所有。装配图网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对上载内容本身不做任何修改或编辑。若文档所含内容侵犯了您的版权或隐私,请立即通知装配图网,我们立即给予删除!