1、Example of a typical E15 SystemCharacteristicsSafe overspeed alarm (SP1) with 2of3 voting (twice), one additional speed alarm signal (SP2) with own 2of3 voter. Safe analog output after 1of3 high level voting. Further Reverse alarm, free Pulse Outputs repeating the sensor signal, Sensor monitor in ea
2、ch channel, Test function control with failure alarms.FunctionNon-contact sensors A, B, C at the turbine shaft detect the speed, transmitting a corresponding pulse frequency to the inputs of the E15 electronics. Its input sections (E1518) make it available, from each channel, to the periphery for ot
3、her use. Isolated, without reaction to the system, and not affected by the test procedure. For instance, to a governor system, or to a remote digital speed indicator. Further, the input modules permanently monitor the sensor circuit, and check for synchronism to the neighbor channels. Failures are s
4、ignalized. The speed monitoring function continues, now with increased intensity 1of2 .Monitors E1555: the central section within each channel: These modules include measurement, alarm triggering, and conversion to analog. Two setpoint alarms are provided, SP1 and SP2, on every E1555. Both individua
5、lly programmable in all aspects as setpoint level, hysteresis, starting and failure condition. Both setpoint signals address one each input of the voter module E1564. For safety reasons, two each E1564 voters are assigned to the overspeed signal SP1 (thus providing two separate shut-down paths). One
6、 voter module serves the SP2 alarm.Each of the E1555 modules further provides an analog signal. All of the three enter one voter E1565. This module selects the highest one of its input signals to transmit it to the periphery mostly a speed governor. This again regards the safety aspect.Applications
7、with own external voting system, will be served by an E15 version, which provides the three original signals separately from each channel.The independent test section includes the test generator module E1593, and the selector E1514. The test generator E1593 supplies a test frequency, representing a
8、turbine speed. Fine adjustable by push-botton starting at a programmable preset. The E1514 module switches this signal by button selection to the input of channel A,B,C, one after the other, to check it from the input to the output. The other channels continue their monitoring duty. The operator obs
9、erves the response of the channel under test.To detect a reverse motion of the machine, a sensor of series A5S3 is installed (“C” in the above diagram.). The E124.1S2 module uses its direction signal, to operate a “reverse motion” alarm contact. Also this function is available with redundancy, using the A5S3. sensors at the other positions, too.
- 温馨提示:
1: 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
2: 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
3.本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
5. 装配图网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。