防火安全矩阵给排水专业毕业设计中英文对照

上传人:沈*** 文档编号:102192702 上传时间:2022-06-06 格式:DOC 页数:37 大小:1,000KB
收藏 版权申诉 举报 下载
防火安全矩阵给排水专业毕业设计中英文对照_第1页
第1页 / 共37页
防火安全矩阵给排水专业毕业设计中英文对照_第2页
第2页 / 共37页
防火安全矩阵给排水专业毕业设计中英文对照_第3页
第3页 / 共37页
资源描述:

《防火安全矩阵给排水专业毕业设计中英文对照》由会员分享,可在线阅读,更多相关《防火安全矩阵给排水专业毕业设计中英文对照(37页珍藏版)》请在装配图网上搜索。

1、本科毕业设计外文文献及译文文献、资料题目:The fire safety design of apartment buildings文献、资料来源:著作文献、资料出版日期:2001院 (部): 市政与环境工程学院专 业: 给水排水工程班 级: 姓 名: 学 号: 指导教师: 翻译日期: 200外文文献:THE FIRE SAFETY DESIGN OF APARTMENT BUILDINGS13 FIRE SAFETY MATRIXThe objective of this fire safety matrix is to provide a guide for the fire engine

2、ering design of apartment buildings. The matrix is only intended for guidance and an appropriately qualified fire safety engineer should verify the final design. The three main fire scenarios that should be considered in the design of apartment buildings are: a smouldering fire in an apartment, a fl

3、aming fire in an apartment and a fire in common spaces (ie stairs and corridors). Irrespective of the building and occupant characteristics, some minimal fire safety measures should be implemented in all apartments. The following is a list of essential fire safety measures that should be provided in

4、 all apartment buildings:1 Smoke detectors2 Heating, ventilation and air conditioning (HVAC) system to shut down on fire alarm3 A 30-minute minimum fire resistance between apartments, vertical shafts and floors.13.1 Emergency strategyBrief descriptions of the emergency strategy, or emergency plans u

5、sed in the matrix are provided below.1 Evacuation on alarm all occupants evacuate the building.2 Non evacuation occupants in the room of fire origin evacuate the building. Other occupants remain in their rooms, waiting for fire brigade assistance and advice, and carry out protect-in-place activities

6、.3 Staged evacuation occupants in the room of fire origin and on the fire floor evacuate first. The remaining occupants are directed to evacuate automatically in the following sequence until the fire brigade intervenes. Occupants immediately above the fire floor evacuate after those on the fire floo

7、r, followed by the floors above. Occupants on levels below the fire floor are evacuated last.Fire brigade intervention can alter the sequence of evacuation, or halt the evacuation in response to current conditions or any changes.13.2 Occupants at riskFor the three fire scenarios and the three emerge

8、ncy strategies, the following matrix outlines the occupants that are most at risk.13.3 Matrix variablesThe fire safety design of apartment buildings consists of numerous variables and interdependencies. These variables have to be considered concurrently to provide the most effective design.The selec

9、tion of fire safety measures in many cases results in a trade-off between various alternatives. For example, sprinkler protection can permit a reduction in fire resistance rating required for buildings and may allow extended travel distances. These trade-offs and interrelationships between fire safe

10、ty measures need to be considered to obtain the most efficient and effective fire safety design.Table 14 lists some of the fire safety measures that should be considered for apartment buildings. The variables presented are not a comprehensive list, and other fire safety measures may be more appropri

11、ate for more complex designs.Table 14 Matrix variables13.4 Buildings greater than 25mThe fire safety matrix for buildings greater than 25m high is presented in Table 15. The matrix provides the recommended fire safety measures for apartment buildings with respect to sprinkler protection and the emer

12、gency strategy. The matrix provides a simple method of determining some of the minimum fire safety requirements of an apartment building. It can also be used to evaluate which type of emergency strategy would be most effective, or when sprinklers would be beneficial given certain building conditions

13、. The justification of the recommended fire safety measures is pvided in Section 14.1.Table 15 Fire safety matrix: buildings greater than 25mthe above matrix are designed to provide at least two levels of protection for the occupants. As the building height increases, the number of fire protection m

14、easures also increases to provide additional levels of protection and maintain the level of safety for the occupants.Table 16 summarises the occupants who are most at risk and the levels of fire safety provided by the above fire safety matrix. Table 17 provides the cell key for identifying the desig

15、nated cells in Table 16. This key remains the same for all cases presented.Table 16 Levels of fire safety (buildings greater than 25m)Table 17 Cell key13.5 Buildings greater than three storeys and less than 25mThe fire safety matrix for buildings greater than three stories and less than 25m high is

16、presented in Table 18. The justification of the recommended fire safety measures is provided in Section 14.2.Table 18 Fire safety matrix: buildings greater than three storeys and less than 25mTable 19 Levels of fire safety (buildings greater than three storeys and less than 25m)13.6 Buildings less t

17、han three storeysThe fire safety matrix for buildings less than three stories is presented in Table 20. The justification of the recommended fire safety measures is provided in Section 14.3.Table 20 Fire safety matrix: buildings less than three storeysTable 21 Levels of fire safety (buildings less t

18、han three storeys)14 DISCUSSION OF FIRE SAFETY MATRIXThe fire safety matrix considers the building height, sprinkler protection and the emergency strategy as the primary variables. This is due to the high influence that the interactions of these variables have on other fire safety measures. In addit

19、ion to this, the fire engineer can specify the emergency strategy and sprinkler protection for the building that will provide flexibility to the matrix. Therefore once the extent of these three variables has been determined the remaining fire safety systems can be selected to suit the building.The o

20、bjective of the fire safety recommendations is to address key issues that result from a given set of building characteristics, while providing multiple levels of protection for occupants in the event of a fire. This provides a backup or redundancy in the design in the event of one part of the system

21、 failing. For example, if the sprinkler system fails the occupants will be protected with passive protection and smoke control systems.The following sections discuss the three building height limits with respect to the fire safety measures that have been recommended. The staged evacuation strategy h

22、as not been discussed separately as it is a combination of the other two strategies and the same fundamental principles apply.14.1 Buildings greater than 25m in height.Once buildings exceed 25m in height, the ability of the fire brigade to rescue occupants externally becomes limited. Therefore, a hi

23、gher level of fire safety needs to be provided to the stairs and escape paths. Emergency lifts are also considered an option to provide rapid access for the fire brigade and egress for disabled occupants.As buildings become taller the level of fire protection needs to increase. This is due to:1 Furt

24、her travel distances, resulting in a higher chance of exposure to fire and fireproducts, and longer exposure time.2 The reduced ability of the fire brigade to rescue people externally3 The increased time for the fire brigade to reach upper levels4 More occupants, resulting in a higher risk of injury

25、 and deaths5 There is a greater variability in occupant abilities and human behaviour, due tothe greater number of occupants5 There are more sources of ignition and fire Evacuation in buildings greater than 25mAn evacuation strategy relies on the protection of egress paths, as well as the protection

26、 of occupants in their apartments before evacuation. The protection of egress paths is critical to ensure occupants are not evacuating through untenable conditions. In buildings greater than 25m high, egress distances can be consider able and therefore, the time occupants spend in escape paths can b

27、e significant.In a sprinkler protected building, protection is provided by:1. The sprinkler system. The sprinklers will activate and extinguish or control the fire, reducing the threat to occupants.2. Compartmentation and mechanical systems. Rooms, corridors and stair shafts are recommended to have

28、a FRR of at least 30 minutes. This will contain the fire in the room of origin and protect occupants before and during egress. Self-closers provided on doors are to ensure the fire does not spread to the corridor. The stairs are to be pressurised to limit smoke spread, provide a partial safe egress

29、paths and provide a smoke free area for the fire brigade.3. The final level of protection is the fire brigade. The fire brigades role would be to assist any remaining occupants and extinguish the fire. A connection n to the fire brigade will be provided to achieve a faster response. In a non-sprinkl

30、er protected building the systems of protection are 2 and 3, as listed above,however the following other fire safety measures will be introduced to increase the level of protection:1. An increased FRR to 60 minutes minimum. This is to provide additional time for occupant evacuation and fire brigade

31、intervention. If occupants choose to stay in their apartments the increased FRR will provide a higher level of protection.2. Connection to the fire brigade. To ensure a faster response by the brigade to a fire.3. Emergency lifts to aid egress and fire brigade access4. Zoned smoke control system. Thi

32、s is to ensure smoke spread through the building is minimised. This should include stair and corridor pressurisation to reduce the chance of smoke spread into the escape paths.5. Lift and stair lobbies to provide an additional barrier against smoke and an area where occupants can wait for lifts or f

33、urther instructions. These areas can be used as refuge areas or other pressurised refuge areas should be provided.6. Emergency warning and intercommunication system. This will allow occupants to communicate with the fire brigade and inform them if assistance is required.7. Additional protected stair

34、s or reduced travel distances, as a trade-off for the limited ability of the fire brigade to externally rescue occupants. Non-evacuation in buildings greater than 25mA non-evacuation strategy relies on the protection of the occupants in their apartments. There is a greater reliance on the fire briga

35、de to extinguish the fire and assist occupants, if evacuation is necessary, during and after the fire is extinguished.In a sprinkler protected building, protection is provided by:1. The sprinkler system.2. Compartmentation and mechanical systems. The rooms are recommended to have a FRR of at least 6

36、0 minutes and to protect the occupants. The fire resistance rating should be designed so complete burn out of the apartment will not result in further fire spread. Self-closers and smoke seals should be provided on all doors opening into corridors. This is to contain the fire in the apartment of ori

37、gin and reduce smoke spread to other apartments. In theory, there will be at least two doors with smoke seals between the fire and occupants.3. The final level of protection is the fire brigade. The building alarm should be connected to the fire brigade to reduce the response time. In a non-sprinkle

38、r protected building the systems of protection are 2 and 3, as listed above, however the following other fire safety measures will be introduced to increase the level of protection:1. Increase FRR to 90 minutes (minimum). This is to ensure complete burnout occurs before further fire spread.2. Emerge

39、ncy lifts to aid egress and fire brigade access3. Lift and stair lobbies to provide protection for the fire brigade, or areas of refuge if occupants choose to escape.4. Stair pressurisation to provide a smoke free path for the fire brigade5. Emergency warning and intercommunication system. This will

40、 allow occupants to communicate with the fire brigade and inform them of any assistance that is required. It will also provide a means for the fire brigade to instruct the occupants.14.2 Buildings greater than three storeys and less than 25mBuildings that are greater than three storeys and less than

41、 25m, have different fire safety issues than buildings greater than 25m. The most notable of these is the fire brigade is able to rescue occupants and fight the fire externally, provided adequate access is provided and a window exists. The travel distances are also reduced, decreasing the time for o

42、ccupants to evacuate and the fire brigade to reach the fire.The transfer of information may also increase, as occupants are relatively closer together.This increases their ability to communicate with other occupants and to perceive visual and audible cues. Evacuation in buildings greater than three

43、storeys and less than 25mThis emergency strategy relies on the protection of the egress paths as well as the protection of the occupants in their compartments before they evacuate. The protection of the egress paths is critical to ensure occupants are not evacuating through untenable conditions. Egr

44、ess travel distances are less and therefore, the duration of occupant exposure to smoke is reduced.In a sprinkler protected building, protection is provided by:1. The sprinkler system.2. Compartmentation and mechanical systems. The apartments, corridors and stair shafts are recommended to have a FRR

45、 of at least 30 minutes. This will protect occupants before and during egress. Self-closers and smoke seals should be provided on all escape path doors.3. The final level of protection is the fire brigade.In a non-sprinkler protected building the levels of protection are 2 and 3, however the followi

46、ng other fire safety measures will be introduced to increase the level of protection:1. Increase FRR to at least 60 minutes to allow the complete burn out of the apartment without fire spread into the corridors or adjacent rooms.2. Self-closers on doors to contain the fire and smoke spread.3. Refuge

47、 areas in stairs for disabled occupants.4. Stair lobbies to provide two smoke and fire barriers for occupants in the stairrefuge areas. Non evacuation in buildings greater than three storeys and less than 25mA non-evacuation strategy relies on protection of occupants in their apartments. There is a

48、greater reliance on the fire brigade to extinguish the fire and assist in the evacuation after the fire is extinguished. The fire brigade can rescue occupants externally via ladders and fight the fire externally.In a sprinkler protected building the levels of protection are:1. The sprinkler system.2

49、. Compartmentation and mechanical systems. The rooms will have a recommended FRR of at least 60 minutes to protect the occupants. The fire resistance rating should be designed so that the complete burn out of the apartment will not result in further fire spread. Self-closers and smoke seals should b

50、e provided on all doors. This is to contain the fire in the apartment of origin and reduce smoke spread into other apartments.3. The final level of protection is the fire brigade. The building alarm will be connected to the fire brigade to reduce the fire brigade response time.In a non-sprinkler pro

51、tected building the levels of protection are 2 and 3, as listed above, however the following other fire safety measures will be introduced to increase the level of protection:1. The fire resistance rating will be increased to at least 90 minutes. This will ensure the complete burn out of the apartme

52、nt can occur without further firespread.14.3 Buildings less than three storeysBuildings less than three storeys are generally the maximum size of a building without lifts.The egress distances in these buildings would typically be within the building codes maximum allowable travel distances, and may

53、not require fire rated stair shafts. The relatively short travel distances result in short movement times, and a fast response fromthe fire brigade on the arrival. If necessary, occupants could also use unconventional escaperoutes, for example garden ladders or climbing down balconies. The fire brig

54、ade can alsorescue occupants externally via ladder and fight the fire externally.The lack of lifts in buildings of this size may limit the number of mobility impairedoccupants that would be present. In general, mobility impaired occupants would be locatedon the ground floor, where they would be able

55、 to escape directly to safety. If disabledThe Fire Safety Design of Apartment BuildingsDepartment of Civil Engineering page 92University of Canterburyoccupants are present, it is recommended that they remain in their apartments and wait forrescue. Therefore, they would use a non-evacuation strategy.

56、 Evacuation in buildings less than three storeysThis emergency strategy relies on occupants escaping quickly. Without fire rated stair shafts the occupants have to travel a relatively short unprotected distance to make final escape.Occupants also need to be protected in their apartments before they

57、attempt to escape.In a sprinkler protected building the levels of protection are:1. The sprinkler system.2. Compartmentation and mechanical systems. The apartments are recommended to have a FRR of at least 30 minutes to protect the occupants before and during their egress. There should also be a FRR

58、 of 30 minutes in the corridors and stairs, if egress distance is in excess of the building codes prescriptive requirements.3. The final level of protection is the fire brigade.In a non-sprinkler protected building the levels of protection are 2 and 3, as listed above, however the following other fi

59、re safety measures will be introduced to increase the level of protection:1. The FRR will be increased to at least 60 minutes. This will ensure the fire does not spread further than the apartment of origin.2. Self-closers and smoke seals will be provided on all doors. This is to contain the fire in

60、the apartment of origin and reduce smoke spread into other apartments.3. A connection to the fire brigade will be provided to achieve a faster response. Non-evacuation in buildings less than three storeysA non-evacuation strategy relies on the protection of occupants in their apartments. For buildin

61、gs less than 3 storeys the fire brigade can rescue occupants externally via ladders and fight the fire externally.In a sprinkler protected building the levels of protection are:1. The sprinkler system.2. Compartmentation and mechanical systems. The rooms are recommended to have a FRR of at least 60

62、minutes and to protect the occupants. The fire resistance rating will be designed so that the complete burn out of the apartment will not result in further fire spread. Self-closers and smoke seals will be provided on all doors. This is to contain the fire in the apartment of origin and reduce smoke

63、 spread into other apartments.3. The final level of protection is the fire brigade. The building will be connected to the fire brigade to reduce the time for fire brigade arrival.In a non-sprinkler protected building the levels of protection are 2 and 3, however the following other fire safety measu

64、res will be introduced to increase the level of protection:1. The fire resistance rating will be increased to a minimum of 90 minutes to ensure the fire does not spread further than the apartment of origin.14.4 Risk and ReliabilityThe assessment of the absolute risk to life safety to apartment build

65、ing occupants is an extremely difficult task. The numerous scenarios, variables, limited data and changes in the risk to life safety during a fire incident, makes an assessment of occupant risk very difficult.Each of the eight elements in Figure 1 will have an impact on the risk to life safety and this level of risk will change during a fire incident. For example occupants on level of fire origin will have a relative

展开阅读全文
温馨提示:
1: 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
2: 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
3.本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
5. 装配图网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
关于我们 - 网站声明 - 网站地图 - 资源地图 - 友情链接 - 网站客服 - 联系我们

copyright@ 2023-2025  zhuangpeitu.com 装配图网版权所有   联系电话:18123376007

备案号:ICP2024067431-1 川公网安备51140202000466号


本站为文档C2C交易模式,即用户上传的文档直接被用户下载,本站只是中间服务平台,本站所有文档下载所得的收益归上传人(含作者)所有。装配图网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对上载内容本身不做任何修改或编辑。若文档所含内容侵犯了您的版权或隐私,请立即通知装配图网,我们立即给予删除!